1. Introduction

Ceramic insulators—particularly porcelain long rods and cap-and-pin disc types—have maintained a significant presence in HVDC overhead line applications due to their proven mechanical reliability and resistance to aging. However, the transition from AC to DC operation introduces a set of electrical and environmental conditions that demand a fundamentally different approach to insulator design and selection. DC pollution performance is markedly inferior to that under AC for equivalent creepage, and the consequences of inadequate dimensioning can be severe, as demonstrated by early operational experience on several HVDC schemes.

2. Application Characteristics Under DC Stress

2.1 Pollution Performance and Creepage Requirements

The most significant challenge for ceramic insulators on DC lines is pollution performance. Unlike AC, where the voltage periodically passes through zero and allows arc extinction, DC voltage maintains a constant unidirectional stress that sustains leakage current and promotes the development of stable dry-band arcs. Consequently, DC insulators require substantially greater unified specific creepage distance (USCD) than AC insulators for the same pollution severity .

Design requirements for DC creepage distance, as specified in IEC 60815-4 or utility specifications, range from approximately 30 mm/kV under light pollution to 50–70 mm/kV under heavy pollution, and can exceed 90 mm/kV in extreme conditions . These values apply to hydrophilic ceramic surfaces. In extreme cases, such as an 800 kV line in an environment with salt deposit density (SDD) of 1 mg/cm², the required total creepage distance can exceed 90 meters, translating to an impractical insulator string length of approximately 27 meters . This reality has driven the adoption of hydrophobic transfer materials (HTM), such as RTV coatings, which can reduce required creepage by 25–60% .

2.2 Electrostatic Particle Attraction

DC electric fields exert a persistent electrostatic attraction on charged particulate matter, causing pollution to accumulate more rapidly and tenaciously on DC insulators than on AC insulators. This phenomenon is particularly pronounced in regions with industrial emissions or airborne dust. The deposited contamination is not readily shed by wind or vibration, and the absence of AC field reversal means there is no periodic repulsive phase to dislodge particles. Field experience from the ±400 kV Bass Link project between Australia and Tasmania illustrates the severity: porcelain long rod insulators initially installed without RTV coating experienced numerous flashovers after energization in the marine environment, and only after RTV coating was applied to all line and station insulators did the flashover events cease .

2.3 Profile and Arc Coefficient Considerations

The shed profile of ceramic insulators plays a critical role in DC performance. Research comparing porcelain long rod insulators (PLRIs) with DC disc types has shown that, while both can achieve comparable pollution performance if correctly designed, the DC disc type exhibits a slightly higher arc coefficient (η), meaning its withstand voltage degrades more rapidly as pollution severity increases . Anti-fog profiles generally outperform outer-rib designs in utilizing creepage distance effectively, though the relationship depends on the specific insulator type and pollution level . IEC 60815-2 provides a framework for evaluating profile suitability, but this standard addresses AC systems; for DC, the profile must be assessed against more stringent criteria due to the higher arc coefficient.

3. Selection Requirements

3.1 Material and Type Selection

The choice between porcelain long rods and cap-and-pin disc insulators depends on the specific application and pollution environment. Porcelain long rods offer the advantage of being non-punctureable, eliminating the risk of conductor drop due to internal insulation failure, and they provide favorable creepage-to-length ratios. Their service record on HVDC lines is well documented: the Baltic Cable (±450 kV), NordLink (±525 kV), and LitPol (±525 kV) projects all employ PLRIs on their overhead sections with good reported performance . In India, PLRIs have operated successfully on the ±525 kV Chandrapur-Padhge line since 1999.

For cap-and-pin ceramic insulators, the selection should prioritize anti-fog profiles with optimized shed geometry. IEC 60815-2 provides guidance on profile suitability, though the standard is written for AC systems and requires correction for DC application. Chinese practice for ±800 kV UHVDC projects recommends 160–420 kN double-shed porcelain insulators for suspension strings in light pollution areas, while composite insulators are preferred in medium and heavy pollution zones .

3.2 RTV Coating as a Mandatory Consideration

Given the severe pollution performance penalty under DC, RTV silicone coating should be regarded as a near-mandatory measure for ceramic insulators in any but the lightest pollution environments. The coating provides hydrophobicity that reduces the effective creepage requirement and mitigates the electrostatic attraction problem. In-factory controlled application is strongly preferred over field application to ensure uniformity and adhesion quality . For existing uncoated installations, field coating has proven effective as a remedial measure, as demonstrated by the Bass Link experience.

3.3 Verification and Testing

Selection should be supported by artificial pollution tests specific to DC conditions. The “up-and-down” method per IEC 61245 allows determination of withstand voltage at expected pollution levels, and comparison across candidate designs provides a rational basis for selection . For projects in severe pollution, full-scale testing of complete insulator strings is advisable, as the pollution performance of individual units may not scale linearly to string configurations.

4. Conclusion

Ceramic insulators remain a viable and reliable choice for HVDC transmission lines, provided that selection accounts for the fundamentally more demanding pollution performance requirements of DC. The key requirements are: substantially increased creepage distance relative to AC practice, careful profile selection to maximize creepage effectiveness, and the routine incorporation of RTV coatings to restore hydrophobicity and reduce dimensional requirements. Field experience from operating HVDC schemes confirms that properly designed and coated ceramic insulators can deliver excellent long-term performance, while inadequately specified units risk repeated flashovers and operational disruption.


 jonsonchai@chinahaivo.com
     sales@chinahaivo.com
     54442019@qq.com
 +86 13587716869
 +86 13587716869
  0086-577-62836929
     0086-577-62836926
     0086-13587716869
     0086-15957720101

QUICK LINKS

PRODUCT CATEGORY

HOT

SUSTAINABILITY

Subscribe to our newsletter

Promotions, new products and sales. Directly to your inbox.
Copyright © 2025 Haivo Electrical Co.,Ltd  Support  by  leadong.com   Sitemap  |  Privacy Policy