165A Low Voltage Pole Mounted Circuit Breaker Adapted To Significant Load Imbalances
Home » Products » 165A Low Voltage Pole Mounted Circuit Breaker Adapted To Significant Load Imbalances

loading

Share to:
sharethis sharing button

165A Low Voltage Pole Mounted Circuit Breaker Adapted To Significant Load Imbalances

The protection and management of MV/LV transformers in rural areas requires the use of specific circuit breakers adapted tosignificant load imbalances, and thus guarantees complete power usage even in unbalanced conditions. These devices (4 poles, three of which are protected) use air-break technology with chambers with metal partitions to cut the arc. Low voltage pole mounted circuit breaker D165T - D265T with a digital trip unit.
Availability:
  • D165T

D165T - D265T

This is a new generation of LV Pole Mounted Breaker developed by HAIVO Electric in accordance with the French market.
This product uses air as the insulating medium, and adopts a knife contact and grid arc extinguishing structure.
Moreover, this product utilizes an integrated digital trip unit in conjunction with a load indicator to achieve the operating time compliant with the HN63-S11 standard and the cumulative overload tripping function.
Users can adjust the integrated digital trip unit as needed, with three power ratings available: 50kVA, 100kVA, and 160kVA.
The external pointer of the load indicator serves dual purposes: displaying load status and allowing users to rotate it to set the required cumulative trip time. This pointer adjustment feature employs stepless adjustment,.offering greater operational convenience.
Users can apply padlocks at the ground-level operating handle to prevent unauthorized personnel from operating the equipment, thereby ensuring power supply security.

LV Pole Mounted breaker/digital trip unit
The protection and management of MV/LV transformers in a rural environment requires specific circuit breakers compatible with significant load differences,thus ensuring full exploitation of the installed power, even in unbalanced operation.

3

Non-contractual document - Manual N2005985D

1-Post circuit breaker with digital trip unit

circuit breakers
D165T D265T
Reference strandard NH63-S-11 NH63-S-11
Voltage rating
Current rating
440V
165A
440V
265A
Cutout power
Closing power
4000A
6800A
6400A
11700A
Number of poles
Number of outputs
4
1 output
4
2 outputs
Cable sections 25/70mm*2 50/150mm*2
Breakdown voltage
• pulse/earth
• at 50Hz
• between poles

20kV
10kV
4kV

20kV
10kV
4kV
Control system Manual Manual
Installation on post on post
Description
Circuit breaker unit
These units (4 poles 3 of which are protected) cut off in air with metal partition chambers to break the arc.
When the circuit breaker is open, a contact makes an electrical link between the transformer neutral and the station structural earth.When the circuit breaker is closed, a spark gap limits the rise in potential of the LV neutral, in relati.n to the structural earthing, for a value exceeding 10 kV.
The circuit breaker is installed inside a weatherproof GRP case.
2 - Digital trip unit

P=50kVA P=100kVA Trip time P=160kVA Trip time
U =440v U =440v U =440v
I=72.2A I=144.3A I=231A
Currant in each phase (in A) Currant in each phase (in A) Currant in each phase (in A)
1 2 3 1 2 3 Min Max 1 2 3 Min Max
Temperature=+20ºC
Initial load 48 48 48 96 96 96

155 155 155

Triphase balanced overload 85
100
160
950
2000
58
58
58
0
85
100
160
950
2000
58
58
58
0
85
100
160
950
2000
120
160
220
950
170
200
320
1900
4000
116
116
116
0
170
200
320
1900
4000
116
116
116
0
170
200
320
1900
4000
240
320
440
1900

1h35
25mn
30s
0.02s
0.02s
1h50
15mn
30s
0.02s


1h10
6mn
0.2s
0.05s

50mn
7mn
0.2s
280
320
500
3000
5640
6400
185
185
185
0
280
320
500
3000
5640
6400
185
185
185
0
280
320
500
3000
5640
6400
400
500
700
3000
55mn
26mn
30s
0.02s
0.015s
0.015s
32mn
11mn
30s
0.02s
1h10
7mn
30s
0.1s
0.025s
0.02s

33mn
4mn
0.1s
Temperature=-25ºC
Initial load 76 76 76 152 152 152

240 240 240

Triphase balanced overload 110
130
190
87
87
87
110
130
190
87
87
87
110
130
190
130
130
130
220
260
380
174
174
174
220
260
380
174
174
174
220
260
380
260
360
480
1h
14mn
30s
2h15
10mn
30s

44mn
5mn

30mn
6mn
350
420
600
280
280
280
350
420
600
280
280
280
350
420
600
420
560
760
1h
14mn
30s
2h15
13mn
40s

45mn
5mn

48mn
5mn40s
Temperature=+50ºC
Initial load 25 25 25 50 50 50

80 80 80

Triphase balanced overload 70
90
160
48
48
48
70
90
160
48
48
48
70
90
160
100
130
200
140
180
320
96
96
96
140
180
320
96
96
96
140
180
320
200
260
400
1h30
20mn
45s
1h
15mn
30s

1h07
5mn

1h
7mn
231
300
500
155
155
155
231
300
500
155
155
155
231
300
500
320
420
650
1h5
17mn
35s
1h
15mn
30s

1h05
5mn
40s

1h
7mn

Trip time as per HN 63-S-11 + corrected values (in bold type) to match the selectivity of the TPC fuses.
Digital Trip Unit
The Digital Trip Unit protects the three ratings of the post-mounted transformer (50 kVA, 100 kVA and 160 kVA) , whether it be a conventional transformer (no internal protection) or a new transformer with protection (TPC).
The transformer protection rating is set by a selector.
The micro-controller assesses the transformer temperature in real time, based on the currents in the three phases and the external ambient temperature. This ambient temperature is computed based on the probe and a mathematical model that is also a function of the three phase currents.

Working Ambient

2 (1)

Temperature: -40°C ~ +70°C
Humidity: 100%
Altitude: ≤2000m
Wind speed :≤40m/s • H
Note: No fire, no explosion hazards, no chemical c.rrosion and recurrent severe vibration.

1b651f

1.lncoming wiring clamp

2.lncoming wiring hole
3.Arc chute grid
4.Operation mechanism
5.Digital trip unit
6.Load indicator trip indication
7.Position indicator
8.Operation handle

1.Incoming wiring clamp
Users can connect the transformer1s low-voltage side or other four-phase (3P+N) power sources as the incoming power supply for this circuit breaker. Additionally, its unique design eliminates the need for users to crimp lugs before connection (as shown on figure 2).
Additionally, the wiring clamps below it serve as outgoing and phase sequence must be ensured during connection.
2. Incoming wiring hole
Users can insert cables into the circuit breaker at this location. Similar to point 1, its lower section is designed for outgoing connections.
3. Arc chute grid
This grid is designed to extinguish arcs during circuit breaker operation. Users can replace this component based on the current condition of the grid.
4. Operation mechanism
This area houses the circuit breaker's operating mechanism. Designed as a spring-charged closing mechanism with a trip-free release, it can be operated via a floor-mounted handle.
5. Digital trip unit
Digital Trip Unit, distinct from traditional thermal trip units or fixed-function PCB hardware trip units, features embedded current transformers with phase-toneutral voltage supply. It complies with the trip response time and accumulated overload response time specified in the HN63-S11 standard. The capacity is configurable to 50, 100, or 160 kVA as required.
6. Load indicator trip indication
The orange component will drop down when the accumulated load time is reached (indicated by Component 6 rotating clockwise past the O position) and Component 10 is in the configuration shown. This action will internally trigger the circuit breaker to trip.
7. Position indicator
The green component protrudes minimally at the bottom when in the closed position.When in the open position, a significantly longer section becomes visible.
8. Operation handle
This handle connects to the floor-mounted operating handle. During installation,users must secure the linkage pin with a split pin. Downward movement initiates tripping/spring-charging, while upward movement performs the closing operation.
9.Load trip enable/disable handle
This handle enables or disables the trip function of the load indicator.
Downward position:
Operate the 9# Operation Handle downward to charge the mechanism, then upward to cl.se the circuit breaker. During this motion, the 7# Load lndicator Trip Indication resets. If the circuit breaker detects overload, the 6# Load Indicator activates When its pointer rotates clockwise past the O position, the breaker trips.
Inward position:
The load indicator continues monitoring but disables tripping.
未标题-2
Figure 4 shows the installation diagram. The floormounted operating handle connects to the circuit
breaker via a standard iron pipe. The illustrated utility pole is circular; if a square utility pole is used,
this must be specified in the installation notes.


Previous: 
Next: 

RELATED NEWS

content is empty!

 jonsonchai@chinahaivo.com
     sales@chinahaivo.com
     54442019@qq.com
 +86 13587716869
 +86 13587716869
  0086-577-62836929
     0086-577-62836926
     0086-13587716869
     0086-15957720101

QUICK LINKS

PRODUCT CATEGORY

HOT

SUSTAINABILITY

Subscribe to our newsletter

Promotions, new products and sales. Directly to your inbox.
Copyright © 2025 Haivo Electrical Co.,Ltd  Support  by  leadong.com   Sitemap  |  Privacy Policy